Loading...
8.1. SR 09-17-2012 Elk REQUEST FOR ACTION River TO ITEM NUMBER Mayor and City Council 8.1 AGENDA SECTION MEETING DATE PREPARED BY General Business September 17, 2012 T.John Cunningham,Fire Chief ITEM DESCRIPTION REVIEWED By Request for Fire Code Variance for Mark and Penny Leadens, Bob Ru recht,Building Official 927 Highway 10 REVIEWED BY Cal Portner, City Administrator ACTION REQUESTED Approve the following fire code variance for Mark Leadens and Penny Leadens ("Leadens") for the property located at 927 Highway 10, Elk River,MN, 55330: • The property shall comply with Chapter 21 of the 2012 version of the International Fire Code (IFC),a copy of which is attached hereto, for the purpose of operating a dry cleaning business. BACKGROUND/DISCUSSION Earlier this month, staff received a request for a fire code variance from Mackall, Crounse &Moore, PLC, of behalf of the Leadens, for the property located at 927 Highway 10, Elk River,MN, 55330. A copy of the variance request is attached. Currently, both the city and state enforce the 2006 version of the IFC. Under the current rules of the IFC, the Leadens would be required to install a sprinkler system at the above referenced property. Changes to the IFC in the 2012 version would exempt the Leadens from having to install a sprinkler system,based on the information provided in the August 30, 2012,letter. Since the state and the city, have not yet adopted the 2012 version of the IFC,the requirements of the 2006 version remain enforceable and the only exemption to the rules are through a variance. While staff strongly encourages and recommends fire suppression systems in commercial occupancies,we understand the financial and practical concerns that often accompany such requirements. In this specific instance,the applicant has,in staff s opinion,provided an acceptable justification for the approval of a variance, based on the changes and requirements set forth in the 2012 version of the IFC. Per § 299F.001, subsection 5, of the Minnesota Statutes, the City Council authorized to grant a variance to the Fire Code (emphasis added): Upon application,the state fire marshal may grant variances from the minimum requirements specified in the code if there is substantial compliance with the provisions of the code, the safety of the public and occupants of such building will not be jeopardized, and undue hardship will result to the applicant unless such variance is granted. No appeal to the state fire marshal for a variance from orders issued by a local fire official from the State Fire Code shall be accepted until the applicant has first made application to the local governing body and the local unit has acted on the application. The state fire FawIRED 0 N:APublic Bodies\City Council\Council RCA\Agenda Packet\09-17-2012\Variance Requestdocx U R E marshal shall consider any decisions or recommendations of the local governing body.Any person aggrieved by a decision made by the fire marshal under this subdivision may proceed before the fire marshal as with a contested case in accordance with the Administrative Procedure Act. Staff has consulted with the state fire marshal's office on this matter and they are in support of this request. The Leadens will still be responsible for adhering to any other applicable fire codes as required in the current (2006) version of the IFC. ATTACHMENTS • Application of Mark and Penny Leadens for Fire Code Variance (August 30, 2012) • Chapter 21, International Fire Code Action Motion by Second by Vote Follow Up N:\Public Bodies\City Council\Council RCA\Agenda Packet\09-17-2012\Variance Request.docx Law Offices Matthew A.Anderson 1400 AT&T Tower Attorney at Law 901 Marquette Avenue (612)305-1401 Minneapolis,MN 55402-2859 maa @mcmlaw.com Telephone:(612)305-1400 N"I Facsimile:(612)305-1414 fly-' www.memlaw.com August 30, 2012 � c � f 12. John Cunningham Elk River Fire Chief 415 Jackson Avenue Elk River, Minnesota 55330 Re: Application of Mark and Penny Leadens for Fire Code Variance Our File No. 092825-00009 Dear Mr. Cunningham: I represent Mark Leadens and Penny Leadens (together, the "Leadens"), who have contracted to purchase certain real property in the City of Elk River (the "City") located at 927 Highway 10, Elk River, MN 55330. The Property was once occupied by a Hardees fast-food restaurant and is now vacant. The Leadens propose to operate a dry-cleaning business at the Property and have applied to the City for a conditional use permit for that purpose. The Leadens respectfully apply for a fire code variance to permit them to operate their dry-cleaning business at the Property without a sprinkler system. The Leadens specifically request a variance from Section 1208.02 of the 2006 International Fire Code ("IFC"), as adopted as the State Fire Code by Minn. Stat. § 299F.011, et seq., and by the City pursuant to Elk River City Code § 22-71, et seq. Section 1208 requires the Leadens to install a sprinkler system at the Property prior to operating the Property as a dry cleaning facility. For the reasons stated below, installation of a sprinkler system is unnecessary to the fulfilling the objectives of the fire coder but will be prohibitively expensive to the Leadens. I. FACTUAL BACKGROUND. The dry cleaning system used by the Leadens is an "Ipura" dry cleaning system using a hydrocarbon solvent with a trade name of Eco Solve. Hydrocarbon solvents have a much lesser environmental impact that the perchloroethylne solvents traditionally used in dry cleaning systems. However, because hydrocarbon solvents are a "Class III" solvent, they trigger the IFC § 1208.02 requirement for a sprinkler system. As noted below, the dry cleaning system used by the Leadens is approved for use under the 2012 version of the ITC without a sprinkler system; is perfectly safe without a sprinkler system; and generates far less environmental contamination than the dry cleaning systems contemplated by the 2006 version of the IFC. A number of jurisdictions in the United States (e.g. Philadelphia) have already amended their ordinances to allow the Leadens' dry cleaning system without installation of sprinklers. The Leadens anticipate that most other jurisdictions will eventually do likewise with the exception granted to dry cleaning systems of this type in the most current version of the IFC. 2 For additional information regarding the Leadens' dry cleaning system, see the manufacturer's website at http://www.columbiailsa.com/ipura.html. Mr. John Cunningham August 30, 2012 Page 2 The dry cleaning system to be used by the Leadens employs advanced machine technology that allows for safe use without the protection of a fire sprinkler system. In fact, the most recent version of the IFC (the 2012 version) approves the use of the dry cleaning system to be used by the Leadens without a sprinkler system. The fire code promulgated by the NFPA does as well. However, as Minnesota continues to enforce the 2006 version of the IFC, the provisions that allow for use of the Leadens' dry cleaning system are not yet applicable in the City. As set forth below, the Leadens satisfy all the prerequisites for the granting of a fire code variance set forth in the governing statute. The dry cleaning system to be used by the Leadens employs machine technology that was not contemplated at the time of the development of the 2006 IFC; is safe for use without a sprinkler system; and is permitted for use without a sprinkler system by the 2012 IFC. Granting the requested variance will allow the Leadens to employ superior, environmentally-friendly dry-cleaning technology with no risk to the public or to the occupants of the Property. Refusing the requested variance will impose hardships on the Leadens that will make their purchase of the Property impractical. For these reasons, and the additional reasons listed below, the Leadens respectfully request that you endorse the granting of a variance from IFC § 1208.02. I1. STANDARD FOR GRANTING VARIANCE FROM STATE FIRE CODE. Chapter 299F of the Minnesota Statutes provides for variances from the State Fire Code, providing in relevant part as follows: Upon application, the state fire marshal may grant variances from the minimum requirements specified in the code if there is substantial compliance with the provisions of the code, the safety of the public and occupants of such building will not be jeopardized, and undue hardship will result to the applicant unless such variance is granted. No appeal to the state fire marshal for a variance from orders issued by a local fire official from the State Fire Code shall be accepted until the applicant has first made application to the local governing body and the local unit has acted on the application. The state fire marshal shall consider any decisions or recommendations of the local governing body. Any person aggrieved by a decision made by the fire marshal under this subdivision may proceed before the fire marshal as with a contested case in accordance with the Administrative Procedure Act. Minn. Stat. § 299F.011, subd. 5 (2012). For the reasons set forth below, all of the requirements necessary for a fire code variance are present here and it is therefore appropriate that the requested variance be granted. J 7tJNT (D[. E,,., Mr. John Cunningham August 30, 2012 Page 3 I11. A VARIANCE IS APPROPRIATE IN THESE CIRCUMSTANCES. The Leaden' dry cleaning system employs safe technology that was not contemplated by the 2006 version of the IFC and complies with the most recent edition of the IFC for use without a sprinkler system. Installation of a sprinkler system at the Property would be prohibitively expensive and would therefore cause undue hardship to the Leadens. For these reasons and the additional reasons stated below, the Leadens respectfully ask that you endorse the Leadens variance application. a. There is Substantial Compliance with the Provisions of the Code. The first requirement for the granting of a variance is that there be substantial compliance with the provisions of the code. Minn. Stat. § 299F.011, subd. 5 (2012). Here, the City's fire inspectors have concluded that the Property fully complies with the State Fire Code with the exception of its non-conformity with IFC Section 1208.02 if the Property is converted to use as a dry cleaning facility. Accordingly, the Leadens fulfill the requirement that the Property substantially comply with the fire code. b. The Safety of the Public and the Buildin14 Occupants Will Not Be Jeopardized. The second requirement for the granting of a variance is that the safety of the public and occupants of such building will not be jeopardized. Minn. Stat. § 29917.011, subd. 5 (2012). Here, IFC Section 1208.02 requires a sprinkler system for "dry cleaning plants containing Type lI, Type I11-A or Type 111-13 dry cleaning systems." IFC § 1208.02 (2006).3 However, the most recent edition of the IFC includes an exception from the sprinkler system requirement for the Leadens' dry cleaning system. The 2012 version of the IFC states in relevant part as follows: 2108.2 Automatic sprinkler system. An automatic sprinkler system shall be installed in accordance with Section 903.3.1.1 throughout dry cleaning plants containing Type II, Type III-A or Type III-B dry cleaning systems. Exceptions: 1. An automatic sprinkler system shall not be required in Type III-A dry cleaning plants where the aggregate quantity of Class III-A solvent in dry cleaning machines and storage does not exceed 330 gallons (1250 L) and dry cleaning machines are equipped with a feature that will accomplish any one of the following: 3 Sections 1203.01 and 1203.02 classify dry cleaning systems in accordance with the flash points of the solvents used in each class of dry cleaning system. IFC §§ 1203.01 and 1203.02(2006). J .L 1L1LL11 t1_LX iXlRE,,,, Mr. John Cunningham August 30, 2012 Page 4 1.1. Prevent oxygen concentrations from reaching 8 percent or more by volume. 1.2. Keep the temperature of the solvent at least 30°F (16.7°C) below the flash point. 1.3. Maintain the solvent vapor concentration at a level lower than 25 percent of the lower explosive limit(LEL). 1.4. Utilize equipment approved for use in Class I, Division 2 hazardous locations in accordance with NFPA 70. 1.5. Utilize an integrated dry-chemical, clean agent or water-mist automatic fire-extinguishing system designed in accordance with Chapter 9. 2. An automatic sprinkler system shall not be required in Type III-13 dry cleaning plants where the aggregate quantity of Class III-13 solvent in dry cleaning machines and storage does not exceed 3,300 gallons (12 490 L). IFC § 2108.2 (2012). (bold text and italics in original) The Leadens' dry cleaning system is certified for compliance with the exception to Section 2108.2 of the 2012 Fire Code identified above. As noted above, the most recent fire code promulgated by the NFPA would also permit use of the Leadens' dry cleaning system without a sprinkler system. Through the adoption and promulgation of the most recent edition of the fire code, the IFC recognizes that neither the safety of the public nor the occupants of the Property will be jeopardized by the use of the Leadens' dry cleaning system without a sprinkler system. Other jurisdictions, most notably the City of Philadelphia, have amended their fire codes to allow the use of the Leadens' dry cleaning system without a sprinkler system. Accordingly, the Leadens fulfill the requirement that the requested variance not jeopardize the safety of the public or the occupants of the Property. c. An Undue Hardship will Result to the Leadens without the Requested Variance. The third requirement for the granting of a variance is that an undue hardship will result to the applicant unless the variance is granted. Minn. Stat. § 299F.011, subd. 5 (2012). Chapter 299F does not define "undue hardship." However, in the context of zoning variances, the Minnesota Legislature recently amended Minn. Stat. § 462.357, subd. 6 to define "undue hardship" as "practical difficulties" created when the applicant proposes to use the subject J CILLVt V U Vl REFT,(' Mr. John Cunningham August 30, 2012 Page 5 property "in a reasonable manner prohibited by the ... ordinance." Minn. Stat. § 462.357, subd. 6. The Leadens certainly satisfy that definition here. The Leadens are proposing to use the Property in a reasonable manner allowed by the 2012 version of the IFC but prohibited by the outdated version of the IFC currently enforced by the State. Installation of a sprinkler system at the Property would require (in addition to the cost of installing the sprinkler system itself) that the Leadens extend a six-inch water line from the Highway 10 water main and make modifications to the design and structure of the building itself. The cost of doing so will be prohibitively expensive for the Leadens and will likely result in the failure of the Leadens' purchase of the Property. Accordingly, the Leadens fulfill the "undue hardship" requirement necessary for the granting of a variance. IV. CONCLUSION. The Leadens will use dry cleaning machine technology that is widely recognized as safe for use without a sprinkler system, but is not allowed by the out-dated edition of the IFC still used by the State. For this reason and the additional reasons stated above, the Leadens satisfy the requirements for the granting of a variance from the State Fire Code. The Leadens therefore respectfully request that you endorse their application for a variance from IFC Section 1208.02. The Leadens will gladly accept that the requested variance be conditioned on the Leadens' use of the dry cleaning system described above that is compliant with the 2012 IFC. For your convenient reference, I enclose copies of Chapter 12 of the 2006 version of the IFC, as well as Chapter 21 of the 2012 version of the IFC. I also enclose a letter from Mary Scalco of the Drycleaning & Laundry Institute International that describes the dry cleaning system technology explains how the more-recently promulgated fire codes allow this technology to be used without a sprinkler system. I adopt this letter by reference in its entirety as part of the Leadens' variance application. Please feel free to contact me at (612) 305-1401 or Pat Steinhoff at (612) 305-1471 if you wish to discuss the foregoing. Thank you for your consideration of the Leadens' request. Very truly yours, MACKALL, CROUNSE & MOORE, PLC Matthew A. Anderson Enclosures cc: Mark Leadens A M L_--tugndry August 28, 2012 Mr. Matthew Anderson Macicall, Crounse &Moore 1400 AT&T Tower 901 Marquette Ave. Minneapolis, MN 55402 Mr. Anderson, It was a pleasure speaking with you last week. IVlany in the drycleaning industry are switching from using perch I oroethylene (pert) to a Class III solvent, especially since now both NFPA and IFC approve the use in certain equipment without having to sprinkler the building. All of the currently available drycleaning solvents other than perc are Class 3 solvents and must be used in machines that are tested and listed for use with Class 3 solvents because they are ignitable. The drycleaning industry has long been involved in the development of the NFPA fire codes and the NFPA committee has worked diligently to make sure the requirements of the NFPA 32 fire code maintain safety as well as recognize the advancements in drycleaning machine technology. The most recent revision of the NFPA 32 code, which has been adopted by the International Fire Code 2012, allows for Class 3 drycleaning machines to be installed in buildings without sprinkler systems if the machine technology meets certain parameters. The reason the industry is moving to a solvent choice other than perc is not that perc is not an excellent drycleaning solvent but there are significant regulatory and media concerns with the use of the solvent and those concerns do not exist to the same extent with the various alternative solvents. There are studies that suggest that exposure to perc in drycleaning can be linked to elevated cancer risks. Of course there are other studies that refute that existence but because of the possibility EPA has extensive regulations in effect for the use of perc in drycleaning. And some states and municipalities most notably California have tightened those regulations. California has banned the use of perc in drycleaning effective in 2020 and currently no new perc drycleaning machines can be installed and there is a phase-out plan in place. In addition to the health concerns,perc is a listed Superfund chemical and any ground or water contamination is subject to extensive and strict cleanup guidelines. Your client is moving to install an Ipura machine and use Eco Solve which is a trade name of a hydrocarbon solvent. Hydrocarbon solvents are effective drycleaning solvents and do not have ........ ....... .................. . .................................... ' the same regulatory and environmental restrictions as pecc, Hydrocarbon aohxeoCs are regulated uou\/OC but the newer hydrocarbon solvents like Bco Solve have less aromatic composition n-taking them less reactive. Also the health risks associated with perc do not exist with hydrocarbon solvents, And any contamination that occursƒr000 the use of hydrocarbon iamuch easier and less costly torccnndio<e because nf its chemical composition. The city of Philadelphia has recently addressed this same issue, did.the research and.came to tl-ie conclusion that tl-ie provisions in the NFPA 32 fire code adequately address the issue of fire safety without the need for the building to have sprinklers. Ploouu lot nuo know iIlcan be of any further uusixia000. Sincerely, � lrig & Laundry Institute Aug 2412 02:10p 763-241-1266 p.1 October 26,2006 Mr.Cliff Anderson Elk River Fire Marshall 415 Jackson Ave. Elk River,MN 55330 Re: 190 Freeport Street Elk River, MN Dear Mr_Anderson: Per our conversation,attached and enclosed is the information we discussed regarding 190 Freeport Street,Elk River,proposed drycleaning business. I was asked by the permit applicant to submit technical data in support of safety requirements of Class III drycleaning systems for your review. We are also aware that the attached documentation will need to be reviewed by other code officials within your jurisdiction,and therefore we trust you can submit its content to the appropriate departments. The drycleaning equipment known as a Colurnbia/ILSA Hydrocarbon System,model TL HCS IPURA is a machine which utilizes a solvent classified as IIIA together with a feature to limit vapor concentration as its safety control system. A Material Safety Data Sheet(MSDS)for two brands of the Class III solvent is enclosed(Exxon/Mobile DF2000 and Chevron Philips EcoSolv). These two solvents are the most widely used within the drycleaning industry and designed for our equipment. For convenience of the interested parties, the following sections of this submittal will reference International Fire Code 2000(IFC),and National Fire Protection Association Standard.for Drycleaning Plants 2004(NFPA32)and then a side note to Uniform Fire Code. IFC.1201.1—Scope requires compliance with Chapter 12 and NFPA 32. IFC 1202—Definitions, solvent or liquid classification Class IIIA solvents, liquids having a flash point at or above 14 0°F and below 20OPF Aug 2412 02:10p 763-241-1266 p.2 Page 2 NFPA 3.3.15.3 Class JIM solvent,liquids having a flashpoint at or above 140°F and below 200T IFC 1203.2— Classification of drycleaning plants and systems. Type ILIA—as systems using Class 111A solvents. NFPA 3.3.18 Systems—Identified in 3.3.18.3 Type IIIA-Systems employing Class 1114 solvent and eomplying with Chapter 4, 5, 6, and 8. 1FC 1207—Drycleaning systems 1247.1 General-Drycleaning systems including units....... shall be installed and maintained in accordance with NPFA 32. The construction of building in which such systems are located shall comply with this section and IBC. 1FC 1208—Fire protection 1208.1 General- .......... shall be in accordance with Chapter 9 1248.2 Automatic Sprinkler System-an automatic sprinkler shall be in accordance with Section 903.3.1.1 throughout drycleaning plant containing Type II,IIIA,or IIIB drycleaning systems. The most obvious difference between the two code standards of IFC and NFPA is that requirements set forth are either Prescriptive(IFC) or Performance(NFPA). In both standards the intent of safety is recognized. The Columbia TL HCS IPURA system is a closed circuit, dry to dry machine and self contained_ This means dry garments are placed into the machine for cleaning and the operator can only start the cycle once the loading door is closed and pneumatically locked. The washing and drying of the work loads can then be executed in an automatic cycle or manual cycle to its completion. When the cycle is finished,the operator will be able to unlock the door and remove dry garments. There is no combustible liquid or vapor present in the ambient of the work(control) area around the machine at anytime. This system is quite different from systems known as"Transfer",where as washing is done in one machine, and the operator must remove wet garments to place there in another unit for drying the garments. In this case combustible vapor and liquid is present in the ambient work(control) area of the equipment. NFPA recognizes the difference of operating equipment within its' scope, and allows for certain building requirements to be relaxed based on the level of hazards that exist in each application;the code standards in IFC uses the higher potential of hazards such as transfer systems and lower flash point liquids and couples them to the least potential of hazards such as closed circuit system with higher flash points and safety controls. Therefore, the following sections of NFPA,32 address the intent of safety in response to the specific equipment configuration and its' control area. 8.1.2.1 —Separation—Type I11A drycleaning plants located in building with other occupancies shall be separated from other occupants by a fire barrier haying a 2 hours minimum fire resistant rating. Aug 24 12 02:11 p 763-241-1266 p.3 .Page 3 Then in: 8.1.2.4—The fire barrier shall be permitted to be a 1 hour with_hours fire protection opening and closing where the question of Class IIIA solvent in the machine and storage to not exceed 330 gallons and provide any one of the safety controls. (3)Features that limit solvent vapors to less than 23 percent ofLEL. 8.1.2.6—Automatic sprinklers shall not be required in drycleaning plants where the quantity of liquid does not extend 330 gallons and any one of the safety conditions. (3)Features that limit solvent vapors to less than 25 percent of LEL. 81.3.3—Electrical equipment and wiring shall be in accordance with National Electrical Code (NEC)for ordinary locations where the equipment contains instrumentation and controls by any one of the following: (3)Features that limit solvent vapors to less than 25 percent of LEL. 8.1.16—Automatic extinguishing system and self closing hatches shall not be required if the equipment contains instrumentation,equipment or controls that independently provide one of the following: (3).Features that limit solvent vapors to less than 25 percent of LEL. As previously stated here within,the difference between code standards of IFC and NFPA can be found in the prescriptive base and performance base methods as to how hazards are addressed. The committee of NPFA 32 spent a considerable amount of time over the past 10 years,updating its' standard to meet the current level of technology within today's drycleaning industry. Today's drycleaning industry is faced with strict rules and regulations regarding air emissions and ground containment of its Class IV solvent,known as perehloroethylene. More then 50%of the industry has already moved from using the non-combustible Class IV solvent to the environmentally friendly Class IIIA. Manufacturers also have made enormous strides in eliminating emissions and spillage of any solvent,regardless of the solvent they are designed to use. In the Class III solvent,manufacturers have incorporated known and sound technologies of safety controls to prevent combustion of these solvents. And since the equipment does not emit vapor or liquids,the need to store solvent inside a building is no longer required. Once a TL HCS 1PURA machine is placed into use, and filled with its liquid, a shop operator will typically not have to add solvent to it for up to a year. Normally solvent is added to an operating system once or twice a year,at no more than 1 to 2 gallons. Naturally this depends on how busy the individual shop is. Solvent within the machine is protected and does not emit to the atmosphere_ Solvent delivery is provided by the solvent manufacturer in metal containers with a capacity of 5 gallons. Aug 2412 02:11 p 763-241-1266 p.4 Page 4 Both IFC and NFPA Code Standards were formulated by the experience and existence of the state of the industry and the technology of the equipment utilizing the solvents. The 100 year experience within the industry shows us that a drycleaning machine has in its process tanks(use)65 and 1000 gallons of liquid depending on the machines dry weight capacity. Additionally,the machine incorporates filters, spinning cycles,heating cycles by high pressure steam,and distillation units. Naturally,with this type of apparatus utilizing a Class IIIA liquid in its process,a keen focus on safety is paramount. The Columbia/ILSA company does indeed build machines as just mentioned; however,the TL HCS IPURA systems;development allows for the elimination of large volume process tanks,high pressure steam requirement, distillation requirement and high RPM spinning requirement. The TL HCS IPURA system holds less solvent than a typical standard automobile's fuel tank. This trivial amount can act as a method to;further reduced the level of control in the area. Never the less,IPURA still conforms with the current standards in IFC and NFPA. It should be noted that prior to the formation of IFC 2000,the 1997 Uniform Fire Code,Acticle 36, drycleaning allowed for exempted amounts set forth in Article 79 for quantities below 334 gallons in unsprinided control areas. We are uncertain as to why the exempted amount was later removed when UFC was meld in to IFC, nor has the IFC Committee substantiated its position in this particular change. In a recent Federal EPA final ruling affecting the drycleaning industry—U.S.Environmental Protection Agency,40 CFR Part 63 EPA-HQ-OAR-2005-0155,published date 7/14106, the department recognized the fire hazard association with Hydrocarbon solvent and cyclic siloxanes, and the technology of the equipment. (See attached EPA Page 91). With this submittal package we ask for a review of the equipment,and the application for permit to construct,with the requirement of automatic sprinklers to be set aside based on this information enclosed. If you have any questions or require more information please let us know directly. We respect the AJH's final decision and we thank you for the opportunity to present this documentation package. Respectfully, ILSA MACHINES CORP. Stephen Langiulli President And NFPA 32 Committeeperson Patrick B. Steinhoff From: Matthew A. Anderson Sent: Friday, August 24, 2012 12:19 PM To: Patrick B. Steinhoff Cc: Mark Leadens; mark leadens Subject: StarTribune article, picked up from Washington Post StarTiribune Science project is taken to the cleaners • Article by: LENA H. SUN • Washington Post • September 3, 2011 -6:29 PM WASHINGTON - Like many memorable science fair projects, it began with a simple idea: Find out what chemicals remain in dry- cleaned clothing. But the problem facing Alexa Dantzler, 15,was that she didn't have access to the proper equipment. So, the sophomore at Bishop O'Connell High School in Arlington, Va., went online. She e-mailed three or four chemistry professors across the country asking for help. Only Paul Roepe, then chairman of Georgetown University's chemistry department, seemed intrigued. He took on the research "for fun." But what started out as something so simple prompted a chain reaction in the university lab: an e-mail exchange, an invitation to collaborate and, last week, a paper published online in a peer-reviewed environmental journal. The paper gives new details about the amount of a toxic chemical that lingers in wool, cotton and polyester clothing after it is dry-cleaned. "At the end of the day, nobody, I mean nobody, has previously done this simple thing--gone out there to several different dry cleaners and tested different types of cloth"to see how much of the chemical persists, said Roepe, who supervised the study. Dantzler, with help from her mother, sewed squares of wool, cotton, polyester and silk into the lining of seven identical men's jackets, then took them to be cleaned from one to six times at seven Northern Virginia cleaners, which had no prior knowledge of the experiment. She kept the patches in plastic bags in the freezer and went to Georgetown once or twice a week to do the chemical analysis with two grad students. The research team found that perch loroethylene, a dry cleaning solvent that has been linked to cancer and neurological damage, stayed in the fabrics and that levels increased with repeat cleaning, particularly in wool. The study was published online Tuesday in Environmental Toxicology and Chemistry. Between 65 percent and 70 percent of the country's estimated 25,000 dry cleaning facilities use the solvent, known as PCE or perc, industry representatives said. Government regulations and voluntary industry guidelines exist for atmospheric concentrations in the workplace, and there has been a long-running fight between environmentalists and the federal government over how quickly the chemical should be phased out for dry cleaners. 1 CHAPTER 21 DRY CLEANING SECTION 2101 5. Type IV—systems using Class IV solvents in which T, GENERAL dry cleaning is not conducted by the public. 2101.1 Scope.Dry cleaning plants and their operations shall 6. Type V—systems using Class IV solvents in which dry cornply with the requirements of this chapter. cleaning is conducted by the public. 2101.2 Permit required. Permits shall be required as set Spotting and pretreating operations conducted in accor- forth in Section 105.6. dance with Section 2106 shall not change the type of the dry cleaning plant. 2103.2.1 Multiple solvents. Dry cleaning plants using SECTION 2102 more than one class of solvent for dry cleaning shall be DEFINITIONS classified based on the numerically lowest solvent class. 2102.1 Definitions.The following terms are defined in Chap- 2103.3 Design. The occupancy classification, design and ter 2: construction of dry cleaning plants shall comply with the DRY CLEANING. applicable requirements of the International Building Code. DRY CLEANING PLANT. DRY CLEANING ROOM. SECTION 2104 DRY CLEANING SYSTEM. GENERAL REQUIREMENTS 2104.1 Prohibited use. Type I dry cleaning plants shall be SOLVENT OR LIQUID CLASSIFICATIONS. prohibited. Limited quantities of Class I solvents stored and Class I solvents. used in accordance with this section shall not be prohibited in Class H solvents. dry cleaning plants. Class IRA solvents. 2104.2 Building services. Building services and systems shall be designed, installed and maintained in accordance Class IIIB solvents. with this section and Chapter 6. Class IV solvents. 2104.2.1 Ventilation. Ventilation shall be provided in accordance with Section 502 of the International Mechan- ical Code and DOL 29 CFR Part 1910.1000,where appli- SECTION 2103 cable. CLASSIFICATIONS 2104.2.2 Heating.In Type II dry cleaning plants,heating 2103.1 Solvent classification.Dry cleaning solvents shall be shall be by indirect means using steam,hot water or hot oil classified according to their flash points as follows: only. 1. Class I solvents are liquids having a flash point below 2104.2.3 Electrical wiring and equipment. Electrical 100°F(38°C). wiring and equipment in dry cleaning rooms or other loca- 2. Class II solvents are liquids having a flash point at or tions subject to flammable vapors shall be installed in above 100°F(38°C)and below 140°F(60°C). accordance with NFPA 70. 2104.2.4 Bonding and grounding. Storage tanks, treat- 3. Class IIIA solvents are liquids having a flash point at or ment tanks, filters, pumps, piping, ducts, dry cleaning above 140°F(60°C)and below 200°F(93°C). units, stills, tumblers, drying cabinets and other such 4. Class IIIB solvents are liquids having a flash point at or equipment, where not inherently electrically conductive, above 200°F(93°C). shall be bonded together and grounded. Isolated equip- s• Class IV solvents are liquids classified as nonflamma- ment shall be grounded. ble. 2103.2 Classification of dry cleaning plants and systems. SECTION 2105 Dry cleaning plants and systems shall be classified based on OPERATING REQUIREMENTS the solvents used as follows: 2105.1 General.The operation of dry cleaning systems shall I• Type I—systems using Class I solvents. comply with the requirements of Sections 2105.1.1 through 2• Type II—systems using Class II solvents. 2105.3. 3• Type III-A—systems using Class IIIA solvents. 2105.1.1 Written instructions. Written instructions cov- ering the proper installation and safe operation and use of 4• Type III-B—systems using Class RIB solvents. equipment and solvent shall be given to the buyer. 2012 INTERNATIONAL FIRE CODE® 201 I DRY CLEANING 2105.1.1.1 Type II, III-A, III-B and IV systems. In be installed in dry cleaning rooms and in drying rooms, Type II, III-A, III-B and IV dry cleaning systems, The ventilation system shall operate automatically when machines shall be operated in accordance with the the dry cleaning equipment is in operation and shall have operating instructions furnished by the machinery man- manual controls at an approved location. ufacturer.Employees shall be instructed as to the haz- 2105.3 Type IV and V systems.Type W and V dry cleanin ,yards involved in their departments and in the work they systems shall be provided with an automatically activated °perform. exhaust ventilation system to maintain a minimum of 100 feet 2105.1.1.2 Type V systems.Operating instructions for per minute (0.51 m/s) air velocity through the loading door customer use of Type V dry cleaning systems shall be when the door is opened. Such systems for dry cleaning conspicuously posted in a location near the dry clean- equipment shall comply with the International Mechanical ing unit. A telephone number shall be provided for Code. emergency assistance. Exception: Dry cleaning units are not required to be pro- 2105.1.2 Equipment identification. The manufacturer vided with exhaust ventilation where an exhaust hood is shall provide nameplates on dry cleaning machines indi- installed immediately outside of and above the loading cating the class of solvent for which each machine is door which operates at an airflow rate as follows: designed. Q=100 x A,D (Equation 21-1) 2105.1.3 Open systems prohibited. Dry cleaning by immersion and agitation in open vessels shall be prohib- ited. Q = flow rate exhausted through the hood,cubic feet per 2105.1.4 Prohibited use of solvent.The use of solvents minute(m'/s). with a flash point below that for which a machine is ALD= area of the loading door,square feet(M). designed or listed shall be prohibited. 2105.1.5 Equipment maintenance and housekeeping. SECTION 2106 Proper maintenance and operating practices shall be SPOTTING AND PRETREATING observed in order to prevent the leakage of solvent or the accumulation of lint.The handling of waste material gen- 2106.1 General. Spotting and pretreating operations and erated by dry cleaning operations and the maintenance of equipment shall comply with the provisions of Sections facilities shall comply with the provisions of this section. 2106.2 through 2106.5. 2105.1.5.1 Floors. Class I and H liquids shall not be 2106.2 Class I solvents. The maximum quantity of Class I used for cleaning floors. solvents permitted at any work station shall be 1 gallon(4 Q. 2105.1.5.2 Filters. Filter residue and other residues Spotting or prespotting shall be permitted to be conducted containing solvent shall r r handled and disposed of in with Class I solvents where they are stored in and dispensed covered metal containers. from approved safety cans or in sealed DOT-approved metal shipping containers of not more than 1-gallon(4 L)capacity. 2105.1.5.3 Lint.Lint and refuse shall be removed from 2106.2.1 Spotting and prespotting. Spotting and pre- traps daily,deposited in approved waste cans,removed spotting shall be permitted to be conducted with Class I from the premises,and disposed of safely.At all other solvents where dispensed from plastic containers of not times,traps shall be held securely in place. more than 1 pint(0.5 L)capacity. 2105.1.5.4 Customer areas. In Type V dry cleaning 2106.3 Class II and III solvents. Scouring, brushing, and systems,customer areas shall be kept clean. spotting and pretreating shall be permitted to be conducted 2105.2 Type II systems.Special operating requirements for with Class II or III solvents. The maximum quantity of Class Type II dry cleaning systems shall comply with the provi- II or III solvents permitted at any work station shall be 1 gal- sions of Sections 2105.2.1 through 2105.2.3. lon(4 L). In other than Group H-2 occupancy,the aggregate 2105.2.1 Inspection of materials. Materials to be dry quantities of solvents shall not exceed the maximum allow- cleaned shall be searched thoroughly and foreign materi- able quantity per control area for use-open system. als, including matches and metallic substances, shall be 2106.3.1 Spotting tables. Scouring, brushing or spotting removed. tables on which articles are soaked in solvent shall have a 2105.2.2 Material transfer. In removing materials from liquid-tight top with a curb on all sides not less than 1 inch the washer, provisions shall be made for minimizing the (25 mm) high. The top of the table shall be pitched to dripping of solvent on the floor.Where materials are trans- ensure thorough draining to a 1 nected to an approved container. 1'12-inch(38 mm)drain con- ferred from a washer to a drain tub, a nonferrous metal drip apron shall be placed so that the apron rests on the 2106.3.2 Special handling.When approved, articles that drain tub and the cylinder of the washer. cannot be washed in the usual washing machines are 2105.2.3 Ventilation. A mechanical ventilation system allowed to be cleaned in scrubbing tubs. Scrubbing tubs which is designed to exhaust 1 cubic foot of air per minute shall comply with the following: for each square foot of floor area[0.0058 m3/(s•m2)]shall 1. Only Class H or III liquids shall be used. a 202 2012 INTERNATIONAL FIRE CODE® DRY CLEANING 2, The total amount of solvent used in such open con- ments of Chapter 57 and be located underground or outside, tainers shall not exceed 3 gallons(11 L). above ground. 3. Scrubbing tubs shall be secured to the floor. Exception:As provided in NFPA 32 for inside storage or 4. Scrubbing tubs shall be provided with permanent 1'/z treatment tanks. inch (38 mm) drains. Such drain shall be provided with a.,trap and shall be connected to an approved container. SECTION 2108 FIRE PROTECTION 2106.3.3 Ventilation.Scrubbing tubs, scouring,brushing or spotting operations shall be located such that solvent 2108.1 General.Where required by this section,fire protec- vapors are captured and exhausted by the ventilating sys- tion systems, devices and equipment shall be installed, inspected,tested and maintained in accordance with Chapter 9. tem. 2106.3.4 Bonding and grounding.Metal scouring,brush- 2108.2 Automatic sprinkler system.An automatic sprinkler ing and spotting tables and scrubbing tubs shall be perma- system shall be installed in accordance with Section 903.3.1.1 nently and effectively bonded and grounded. throughout dry cleaning plants containing Type II,Type I11-A 2106.4 Type IV systems. Flammable and combustible liq- or Type 111-B dry cleaning systems. uids used for spotting operations shall be stored in approved Exceptions: safety cans or in sealed DOTn-approved shipping containers 1. An automatic sprinkler system shall not be required ' of not more than I gallon (4 L) in capacity. Aggregate in Type III-A dry cleaning plants where the aggre- amounts shall not exceed 10 gallons(38 L). gate quantity of Class III-A solvent in dry cleaning 2106.5 Type V systems. Spotting operations using flamma- machines and storage does not exceed 330 gallons ble or combustible liquids are prohibited in Type V dry clean- (1250 L) and dry cleaning machines are equipped ing systems. with a feature that will accomplish any one of the following: SECTION 2107 1.1.Prevent oxygen concentrations from reach- ing 8 percent or more by volume. DRY CLEANING SYSTEMS 2107.1 General equipment requirements. Dry cleaning 1.2.Keep the temperature of the solvent at least 30°F(16.7°C)below the flash point. systems, including dry cleaning units, washing machines, stills, drying cabinets, tumblers and their appurtenances, 1.3.Maintain the solvent vapor concentration at a including pumps, piping, valves, filters and solvent coolers, level lower than 25 percent of the lower shall be installed and maintained in accordance with NFPA explosive limit(LEL). 32.The construction of buildings in which such systems are 1.4.Utilize equipment approved for use in Class located shall comply with the requirements of this section and I, Division 2 hazardous locations in accor- the International Building Code. dance with NFPA 70. 2107.2 Type H systems. Type II dry cleaning and solvent 1.5.Utilize an integrated dry-chemical, clean tank storage rooms shall not be located below grade or above agent or water-mist automatic fire-extin- the lowest floor level of the building and shall comply with guishing system designed in accordance with Sections 2107.2.1 through 2107.2.3. Chapter 9. Exception: Solvent storage tanks installed underground, 2. An automatic sprinkler system shall not be required in vaults or in special enclosures in accordance with Chap- in Type 111-13 dry cleaning plants where the aggre- ter 57. gate quantity of Class III-B solvent in dry cleaning 2107.2.1 Fire-fighting access.Type 11 dry cleaning plants machines and storage does not exceed 3,300 gallons shall be located so that access is provided and maintained (12 490 L). from one side for fire-fighting and fire control purposes in 2108.3 Automatic fire-extinguishing systems. Type II dry accordance with Section 503. cleaning units, washer-extractors, and drying tumblers in 2107.2.2 Number of means of egress.Type H dry clean- Type 11 dry cleaning plants shall be provided with an ing rooms shall have not less than two means of egress approved automatic fire-extinguishing system installed and doors located at opposite ends of the room,at least one of maintained in accordance with Chapter 9. which shall lead directly to the outside. Exception:Where approved, a manual steam jet not less 2107.23 Spill control and secondary containment. than 3/4 inch(19 mm)with a continuously available steam Curbs,drains or other provisions for spill control and sec- supply at a pressure not less than 15 pounds per square ondary containment shall be provided in accordance with inch gauge (psig) (103 kPa) is allowed to be substituted Section 5004.2 to collect solvent leakage and fire protec- for the automatic fire-extinguishing system. lion water and direct it to a safe location. 2108.4 Portable fire extinguishers. Portable fire extin- 2107.3 Solvent storage tanks. Solvent storage tanks for guishers shall be selected,installed and maintained in accor- Class II, IIIA and IIIB liquids shall conform to the require- dance with this section and Section 906.A minimum of two, 2012 INTERNATIONAL FIRE CODE" 203 DRY CLEANING 2-A:1O-B:C portable fire extinguishers shall be provided near the doors inside dry cleaning rooms containing Type 11, Type III-A and Type III-B dry cleaning systems. 204 2012 INTERNATIONAL FIRE CODE