6.3. ERMUSR 09-11-2007J~ Elk River -~= Municipal Utilities 13069 Orono Parkway • P.O. Box 430 Elk River, MN 55330-0430 September 5, 2007 To: Elk River Municipal Utilities Commission Jerry Takle Jerry Gumphrey Jim Tralle From: Bryan Adams Subject: Maintenance Issues Phone: 763.441.2020 Fax: 763.441.8099 In the process of constructing our proposed 2008 capital budgets, we found some maintenance items that should be addressed. These items are building roof inspections, substation maintenance and water treatment plant electrical inspections. The roofs of our operations area and six water treatment plants have not been recently inspected and we know we have leak issues at two of our treatment buildings. McDowell Company will inspect and provide a report and necessary cost estimates for $979.00. This is part of a roof management program they offer. Staff recommends we do this inspection on an annual basis. We have been building substations on a regular basis but have been poor at doing annual maintenance. We are proposing to use Utility Plus in Elk River to do a complete substation maintenance program at a cost of approximately $15,000 per substation. With seven substations, we are proposing to do one substation per year. This will include 69KV circuit breaker, inspection and testing, transformer and LTC testing, inspection and filtering oil, re-closure inspection testing and lubricating. We are proposing to start this program late this fall. In the water department, we perform maintenance on one well per year resulting in a seven year cycle at an approximate cost of $25,000/year. Unfortunately we have never looked at the electrical panels in the filter plants. Due to the wet conditions and presence of chlorine and fluoride, both very corrosive, the condition of the electrical gear and protective system is in question. Dymax, a St. Paul company is proposing to do a complete inspection, lubrication, verify connection, check trip devices and clean electric gear in all seven facilities at a cost of approximately $12,500. Staff recommends this work be initiated late this fall. HuU ca-~uu i wl;u u~: 4iJ t'I1 f1cUUWALL COMPANY FAX N0, 3202519317 ERING the ements /1u~ust 2~), 2UU7 1?ll: l~.iver lt'lr~riicil~,~.rl [Itililic:s t fC}~'ir) ()rc.raio l'rttbcw~r~y 1,llc ltivcr. M~1 x,53;1() Altcrard.i~rn 1~3r-yan .~rrJr3crr,, I'.1~.: Rl~: ltouJ' Asscssa~t<:rat P, 02 'l'fa~ liall(r~vir7~, is ;.t JZ(scr( fVlrtar<y~crr~crtt 1'm~;rarn that McDowall Company offers with :r ctcscripti(~n rtaril quc-ic~ the l:~ll~ I'~ivc~r Mrrnis.~-ilyAal [ltiJitics lacilitics including; both buildin~,s at the C'nwcr I'larrt iiricl alJ 6 ~vcll hou,scs that ~x/l"r`i.', Slat"1I~;yC';~~ t~a7 1~%7~), ~~~1 ~~ YYYaYNwtkw,~t,YYE~~iHl~~lyd>~~'~OYy~l~irbS~'T~CV.ibYi OZYCC i[ ~di' l~ti(tictl It1,;I~t/~,li(lr'1 d~~rrc i~nc;~~ a year with an an.nu,al report 1. GL-a'tR:r~r.l rix~l"irr(irrai~~.rlii~n ~- I'`iti~c' car tc°s~ yc;~r• rcl~,~ir ar,d re-roof btrdg;cts 3, ~hrcraa~r:lrr1y itr(arrr•t;r.iiort (ati availal~lc) ~~. ~~c-rk, laltitr}ty i. }3~:~f'r~~,t~; wil.l•r J~icllsrc.5 ti, lr-,:;I•t~;cttc>rt t1.~:~,ck;s,aacraks '1'hc regrc~rt includes the followiraf;: !. R~,:c('ratrrtr~~ar~~r,titarr:~ ~l. [,Jsz;a•-fa°i,;(~alJy c(~r~~plrte:r ~ollwarc systcnr to vrcw and update ypur ('utility rClx)rt !!~[cJ.'~ti~~~a11 C'ni~~l--<rny will work with your facility a~iartri~;e;rs to set-up report prop,rranls t(~ Iit your aaeccis. n. raol tr1S~'~~"CI101-4 la-rr,~,lroclc. Ilx~ ihllr~wing;: llarr,lr,r,l in~l>cc:licaal: (. (:ntrclr.at~k ru(,rCin,vc~;l.i~~aiiun using roof inspection ~uitlc a. ~t`1•iut-c~rik«lrly cle.;.ck rill roof penclrrdtic~n 1l~r.Shin~s [~. 'llt(~rulrg)~ily clrcck all roofpcrimc:te;r alas}lin~?s c. '1'laor(,ur;hly e;l7i;c1< ~rll scuppers and draira f7a51iirig;s cl. i~lrzl~~ (,hvi(,us l~roblcros wish rriof f3ccestinries u. `1`,:~rY7}>iri<try repair (ifalrplicablc) (`. M~~~k~: r~~I3:iirs ti) rjny dclc;cts undor the rltia.nraf~icturers warranty ~. l;t:rrt~~vw <'(t~hri;; ('rc'rrri rool-clrains and scu(~pca•s :3. It~=rt'rc>vrr aic}r'msrl ru(~fint; debris from roof (bra.nthrs, be~ti(ts, wise...) this does nat inclracic~ debris tauscd Iyy olhc~r fr~rcls~s c,r r•crrtu(lcling, ~1. P,'~~:lurr~;, r7,rFa~or.r;o1 rcpc~rt (car- lac prc~parccl spria~~; or full) ~~, l'r'cla~~rc r,;(~air,~(:~,Iu; i('rc~c>fnccds aayy itnmcdi4ate repairs ~, ~,,~,:~ F-c~c}f~it~~i ~ ~Y ~'~~~c~l~ing 'l~Air C;ondifioning ,~~ Energy M:~rtager-nenl ; ,,;i~'~~~~~/~ iiuU c~ cuu i wcu uu ~ ~~ rfl 1"ICUUWHLL liUflt'HIVY t•HX NU, ~CU'L~ 1 y~l ( P, Q3 T?ll~~ f~iv~:-~ A~4-,Irli~„iybtil rJlilitics 1'tsC;;~~ ~ 'C"!tc ~~c~st .I[~r iCa., t4t;i~vc;-,ttc,--iiz~tic~l st,rvice would lac N1NL 11UN1)RI~D ANI) ~F,VI;;;I~!'1'Y 1'~1}~11+; 1)()I.,l,Alz~- `l'l~li'l~'~1(li; 6;~; I'~~t} ),,(~)lY(; '1'r±..IZI~VI AGlzl':1~1V11+;N'1' Wl'1'rri MCDOWA1.1a C'(}Ml'A-NY; ,1,1,1 q((DtpF C~l/S.J°J~d.el~~g~1F;1~1"1' AC;~i~zt+..i~:Mi~aN'1'~ Altl+l !tr!;h'1;WE1) 1'EAR1.Y r;V ~il'Vllkl~Y 1'~Y11'~l~(: ~'()l,Ilt 1N~'d•)~d:;l~,. lit.)(}?E+' ]~lR-NA(~t+.1411;1~i'1" A(:IlF~T+;MC!;1V'1'ti MAY liL+' C.ANCELI,Ff) 131r :~q:~~Nl)rNd: IN A ~r~b~~"~l~lt~.i~ N(~'rl~;r+, W.r°rl~a ~c~ura r:urar{r.N'r tNVOtc~~. 1NVOlcc~ htzr~; st{;N'~1' ()tr'1' oi`l ,,~e8i~[ar°~~~~' C - t:)l+' q~,/~,.1"~1~0 'Yl?Ald. 7'1-11; F'11z~T' Il'VVOIC +' W1LL Lll ~1:1~1'lf' ()I1'f' 1''I~l()1~E '1'() 'l'lll~~ 1r'11~:~'1' 6,'~'~t~l~;(„~l'l(1N Ol+,'1'1'11+ 1tUU1~ IVIANA(:1+,1M1+:N'1' 1'ROGftAI'vl. l.tz'yc-~'t, C•ill~;o;~;~~ c:~l- 'if y~a~i Il%11~'CG f~7iy (t~c~re questions rcf;~trdin~; titi~ rpvf• mainlcnancc ~tl~ 11.11nEi~;~'i11C',1-t ~r•u~,i~t~n. C'7~~esc ,sign, ii~Cr tteu,! 'f~•t.~c 1'~:a~k tcy Mcf)owall Comapany if'yoet zicccpt this ~rest~c~sal. A ]yard cosy will lac sc:rrt iii (Pay; Fa~I~,il. '1'~ttr.rak Yc~«, MGhOWALL CO14~dPAN~Y Tom Mc17c1wa11 (320) 251-3C~1(? n~al.e: Utilities Plus Energy Services, Inc. 16864 Highway 10 W Elk River, MN 55330 Phone: 763-441-1200 Fax: 763-441-7500 August 8, 2007 Troy Elk River Utilities RE: Testing, calibration, and maintenance on your West substation ;~ . ,, Dear Troy, With regards to your interest in Utilities Plus Energy Service performing the above testing and calibration at your facility we propose the following; (1) SF6 Circuit Breakers • Perform testing on (1) SF6 circuit breakers • Perform all mechanical checks • Perform time travel analysis • Perform optional gas analysis *** • Check breaker contact resistance with a 400amp ductor • Check insulation integrity Perform lubrication of mechanical parts (1) Transformer • Perform testing on (1) transformers • Perform visual inspection • Test operate all auxiliaries • TTR • Power Factor • Oil analytical LTC test and inspection: Testing and inspection will include the following A) Drain LTC chamber into drums B) Open LTC compartment and clean. C) Inspect reversing contacts, movable contacts, stationary contacts, all leads and connections, vacuum bottles and or resistive circuit. D) Filter oil back into LTC E) Furnish a report with the findings. Protective scheme for reclosures o Clean relay o Perform Pick-up and Drop-out tests o Perform timing tests at 2 points on the curve o Clean contacts o Calibrate and make minor setting changes if needed Reclosures (4) o Drain oil o Inspect tank o Inspect contacts and or vacuum bottles o Lubricate mechanism o Perform vacuum bottle integrity test o Perform contact resistance checks o Perform operational checks Total price for all of the above work performed on Straight time I have broken out the pricing if you decide not to perform parts of the maintenance: - SF6 Breaker maintenance - SF6 gas samples - Transformer maintenance Power Factor test TX - Reclosure and rely maintenance - LTC maintenance $ 720.00 $ 350.00 " ~ '~-{- Z `~ ~ $ 600.00 ~ ~ $ 450.00 $ 3,200.00 on site $ 1,890.00 Our proposal is based on straight timework and expires in 60 days. Tax and freight not included This proposal is subject to Utilities Plus Energy Service terms and conditions of sale form UP41700. If you have any questions or concerns feel free to give us a call. Sincerely, Ron Mingo President of Operations ~`,~ ~ ~,r-`~ w- `~ ~. 5-~~ ~~~ ~p~~ f L ~ ~ ~ V- w ~: ~~. ~~ ~ ~ ~ ~~ s 2 _t~~,~ ~ DYMAX Service, Inc. ~;,c LL ~. j~'~ . Mustang Circle • St. Paul, MN 55112 • 763-784-4040 --~""~ ---- Fax 763-784-5397 Quotation No. 18011 July 19, 2007 Mr. David Berg Elk River Municipal Utilities 13069 Orono Parkway Elk River, MN 55330 Dear Mr. Berg: With regard to your interest in quotation for Water Department Electrical Checks, Maintenance Testing and Infrared Inspections for Elk River Municipal Utilities, we propose the following: Electrical Inspection, Maintenance Testing & Thermographic Survey 1) Visual and Mechanical Inspection a) Inspect for physical, electrical, and mechanical condition; b) Visually inspect for bus alignment. c) Remove all necessary covers prior to scanning 2) Equipment to be Scanned: Well 4, 5 and 6 Electrical Equipment { Each of wells 4, 5, and 6 has the following electrical equipment installed: } • Allen Bradley Motor Control Center Centerline MCC, 3-Section, consisting of: • (1) Spare/Blank MCC Bucket • (1) Power Monitor MCC Bucket • (3) Size 0/ Size 1 combination starter/disconnect buckets • (4) Size 1 /Size 2 combination starter/disconnect buckets Well 2 and 3 Electrical Equipment { Each of wells 2 and 3 has the following electrical equipment installed: } • (1) Square D Type SFG1 40 H.P. Nema 1, Size 4 240V Enclosed Combination Starter/Disconnect w/HOA and Pilot Devices • (1) ITE 18-circuit Panel w/ 15A & 20A single pole circuit breakers • (1) 225A Main Breaker Square D Circuit Breaker Panelboard consisting of: (1) 225A Main CB (10) 15A to 150A Molded-Case Frame Circuit Breakers Quotation No. 18011 July 19, 2007 Well 7 and 8 Electrical Equipment { Each of wells 7 and 8 has the following electrical equipment installed: } • Allen Bradley Motor Control Center Centerline MCC, 4-Section, consisting of: • Section One -Six MCC starter buckets • Section Two -five MCC starter buckets • Section Three -five MCC starter buckets • Section Four -three MCC starter buckets • (1) ABB 225 Horsepower VFD 3) Provide Report Indicating the Following: a) Problem area (location of "hot spot"). b) Indicate temperature rise between "hot spot" and normal or reference area. c) Indicate cause of heat rise. d) Indicate phase unbalance, if present. e) Index of areas scanned. 4) A DYMAX NETA certified technican will be removing covers and performing the visual inspections as the Infrared Survey is taking place. Molded Case Circuit Breaker, 100 Amp 8~ Above 1) Check equipment ground to assure continuity. 2) Visually inspect breaker and operate manually. 3) Check for proper lubrication. 4) Check all arc chutes as needed. 5) Check all connections for tightness. 6) Blow dust and dirt from breaker and arc chutes. 7) The trip devices shall be high-current tested as follows. a) Long time delay element: (if applicable) Apply a current of 3 times the LTD pick-up value to each pole, recording current and times required for breaker to trip. b) Short time delay element: (if applicable) Apply a current of 1.5 times the STD pick-up value to each pole, recording current and times required for breaker to trip. c) Instantaneous element: (if applicable) Test by applying a rapidly increasing current, recording value which caused breaker to consistently trip instantaneously. d) Ground Fault element: (if applicable) Apply a test current of sufficient magnitude to ensure proper trip time given breaker settings. 8) Contact resistance will be measured with the use of a low resistance ohm meter. 9) Furnish report. Motor Starter and Contactors) 1) Check equipment ground to assure continuity of connections. 2) Check closing coils for proper operation. 3) Clean all contacts and magnetic surfaces. 4) Blow dust and dirt from contactor and arc chutes. Page 2 of 3 Quotation No. 18011 August 2, 2007 1) Check air gap between moving and stationary magnets. 2) Check all auxiliary contacts for correct arrangement. 3) Test each pole of starter for freedom from grounds. 4) Test contacts to verify low resistance connection. 5) Test motor overload relays. 6) Furnish report. Price for Services $12,410.00 Price does not include applicable local, state or federal tax. This price is quoted for straight time work and expires in 30 days. DYMAX is a NETA (International Electrical Testing Association) Certified Company. DYMAX's testing programs are exceptionally thorough and performed by trained, NETA certified field engineers and technicians. Payment terms are Net 30 days from date of invoice. Overdue accounts will be charged interest at a rate of 1.5% per month. DYMAX warrants that any work performed and any material provided shall be free from defects under normal use for a period of 1 year. DYMAX shall repair or replace, in its sole discretion, any product provided by DYMAX that it determines was defective provided it receives written notice of such defect during the warranty period. DYMAX shall not be responsible for any kind of indirect or consequential costs or damages. The terms and conditions of this quotation supercede any conflicting terms of subsequent purchase order. We appreciate this opportunity to quote and look forward to being of service to you in the near future. If you have any questions, please do not hesitate to contact me, or Mark Charron your Account Manager. Sincerely, Michael Mavetz Vice President Page 3 of 3